Balancing Valve
Design Features
Balancing Valve is a Double Regulating, Control and Shut-off Valve with built-in pressure drop measuring (in line flow measuring) facility. Balancing problems are quite evident in a Multi-User systems, like Central Air Conditioning Plants and in Process Heat Exchangers. The Valve is a combination of a Shut-Off Valve (Gate/Plug/Ball/Butterfly Valve) plus Flow Regulating Valve (globe Valve) and Flow Measuring Station and also a Drain Cock (available in Bronze Valves only). It is not merely a Valve but a system in itself. It provides a scientific basis for Flow Balancing in a system with database. The Valve can be set in pre-regulated flow conditions for Tamper-Proof positioning by a Built-in Locking Device. The Valves are extensively used HVAC systems and other process applications wherever balancing problems exists.
Balancing Valve TO-01 Specification
| Part No. |
Name of Part |
Material |
| 1 |
Body |
Cast Iron |
| 2 |
Bonnet, Cover |
Cast Iron |
| 3 |
Cover O-ring |
Rubber |
| 4 |
Spring |
Stainless Steel |
| 5 |
Disc Rubber |
NBR |
| 6 |
Disc Holder |
Cast Iron |
| 7 |
Packing |
Bronze |
| 8 |
Indicator |
Iron |
| 9 |
Valve Stem |
SS304 |
| 10 |
Cover Bolt |
SS304 |
| 11 |
Hinge Stem |
Stainless Steel |
| 12 |
Packing |
Cast Bronze |
| 13 |
Screen |
SS304 |
| 14 |
Bypass |
Brass |
TO-01 Technical Data
| |
TO-01 |
| Applicable Fluid |
Water, Oil |
| Applicable Inlet Pressure |
Max, 10kg/c㎡ |
| Applicable Temperature |
Max,82≧
(Special Order: Max 120≧ |
| Min, Pressure Differential across the Disc |
0.04----0.07kgf/c㎡ |
| Leakage Allowance |
0 |
| End Connection |
ANSI B16.1 CL125, BS4504 PN10 |
| Hydrostatic Test |
15kgf/c㎡----3min |
|
Balancing Valve
Performance Feature
Specifications
Dimensions
|